View all FAQs
How does water conductivity affect the performance of my steam humidifier?
- Category:Humidifiers
Steam cylinders must be matched to the local water conductivity in order to perform as designed. If not familiar with local water conductivity, check using an instrument ( EZTestr11 Conductivity Tester). You can also have your water tested for conductivity by the city or a local contractor.
The following water types are not acceptable:
- Softened water, as this will lead to foam, electrode corrosion and greatly shortened cylinder life.
- Water containing disinfectants or corrosion inhibitors, as these are potential irritants.
- Industrial water, boiler water or water from cooling circuits.
- Any potential chemically or bacteriologically contaminated water.
- Heated water.
- Water with silica deposits.
- Pressure between 20psi and 110psi; or 0.1 and 0.8 MPa (1 and 8 bar)
- Temperature between 33° F and 104° F; or 1° C and 40° C
- Flow rate minimum of 0.45 L/min or 0.21 gpm
- Hardness no greater than 40° fH (equal to 400 ppm3 of CaCO),
- Conductivity from 125 to 1250 µS/cm
- Absence of organic compounds